Omnizone™ Constant Volume Water-Cooled Cooling Unit 50BVJ: Monthly Maintenance
This monthly maintenance procedure focuses on air filters. It gives you instructions on how to inspect the air filters and how to replace them.
Omnizone™ Constant Volume Water-Cooled Cooling Unit 50BVJ: Monthly Maintenance
This monthly maintenance procedure focuses on air filters. It gives you instructions on how to inspect the air filters and how to replace them.
Air Filters
The 50BV single-piece units come with 1-in. filters. The standard 1-in. filters provide lower pressure drop and longer filter service intervals. The 50BV modular units come with 4-in. filters.
Inspect air filters every 30 days and replace filters as necessary.
Replacement filters should have a minimum efficiency rating of MERV 6 per ASHRAE rating procedures and be rated for up to 625 fpm velocity. Job requirements or local codes may specify higher minimum ratings.
Source: Carrier (www.shareddocs.com)