This procedure is for the maintenance of your Microchannel Heat Exhanger. The list on how to maintain and clean your condenser coil are included. Simple routine maintenance as described in this procedure will enhance your air conditioning system’s ability to operate economically and dependably
Gemini® Select Air-Cooled Condenser 09DP: Microchannel Heat Exchanger (MCHX) Condenser Coil Maintenance and Cleaning Recommendations
This procedure is for the maintenance of your Microchannel Heat Exhanger. The list on how to maintain and clean your condenser coil are included. Simple routine maintenance as described in this procedure will enhance your air conditioning system’s ability to operate economically and dependably
! CAUTION
Do not apply any chemical cleaners to MCHX condenser coils. These cleaners can accelerate corrosion and damage the coil.
Routine cleaning of coil surfaces is essential to maintain proper operation of the unit. Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit.
The following steps should be taken to clean MCHX condenser coils:
! CAUTION
Excessive water pressure will fracture the braze between air centers and refrigerant tubes.