Carrier INFINITY® 96 GAS FURNACE 59TN6 Yearly Maintenance

The Carrier INFINITY® 96 GAS FURNACE 59TN6 Yearly Maintenance form is used to check your equipment's performance. This form is sectioned by the different parts of the equipment with individual checkists for thorough inspection ensuring not just performance but safety for both your company and employees.
MaintainX
04/26/2021

Carrier INFINITY® 96 GAS FURNACE 59TN6 Yearly Maintenance

The Carrier INFINITY® 96 GAS FURNACE 59TN6 Yearly Maintenance form is used to check your equipment's performance. This form is sectioned by the different parts of the equipment with individual checkists for thorough inspection ensuring not just performance but safety for both your company and employees.

    WARNING: FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Never store flammable or combustible materials on, near, or in contact with the furnace, such as:

    1. Spray or aerosol cans, rags, brooms, dust mops, vacuum cleaners, or other cleaning tools.

    2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene, cigarette lighter fluid, dry cleaning fluids, or other volatile fluids

    3. Paint thinners and other painting compounds, paper bags, or other paper products. Exposure to these materials could lead to corrosion of the heat exchangers.

    For continuing high performance and to minimize possible furnace failure, periodic maintenance must be performed on this furnace. Consult your local dealer about proper frequency of maintenance and the availability of a maintenance contract.

    WARNING: ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or s

    WARNING: CARBON MONOXIDE POISONING AND FIRE HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Never operate furnace without a filter or filtration device installed. Never operate a furnace with filter or

    CAUTION: vCUT HAZARD Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts, and servicing furnaces.

    The minimum maintenance on this furnace is as follows:

    Cleaning and/or Replacing Air Filter

    WARNING: CARBON MONOXIDE POISONING AND FIRE HAZARD Failure to follow this warning could result in personal injury, death and/or property damage. Never operate furnace without a filter or filtration device installed. Never operate a furnace with filter or

    NOTE: If the filter has an airflow direction arrow, the arrow must point toward the blower. To clean or replace filters, proceed as follows:

    WARNING: ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death, or property damage. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF positi

    Blower Motor and Wheel Maintenance

    To ensure long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.

    The inducer and blower motors are pre--lubricated and require no additional lubrication. These motors can be identified by the absence of oil ports on each end of the motor. The following items should be performed by a qualified service technician. Clean

    Disconnect the vent and combustion air pipe by:

    See Fig. 67 for Steps 5 through 14.

    NOTE: Blower wheel is fragile. Use care.

    If greasy residue is present on blower wheel, remove wheel from the blower housing and wash it with an appropriate degreaser. To remove wheel:

    NOTE: Mark blower mounting arms and blower housing so each arm is positioned at the same hole location during reassembly.

    NOTE: Be sure to attach ground wire and reconnect blower harness plugs to blower motor.

    WARNING: ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Blower door switch opens 115--v power to control. No component operation can occur unless switch is closed. Caution must be taken when manually c

    Downflow or horizontal furnaces with vent pipe through furnace only:

    NOTE: If R--W/W1 thermostat terminals are jumpered at the time blower door switch is closed, blower will run for 90 sec before beginning a heating cycle.

    Cleaning Burners and Flame Sensor

    The following items must be performed by a qualified service technician. If the burners develop an accumulation of light dirt or dust, they may be cleaned by using the following procedure:

    NOTE: Use a back-up wrench on the gas valve to prevent the valve from rotating on the manifold or damaging the mounting to the burner assembly

    WARNING: ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or s

    Refer to Fig. 68.

    To reinstall burner assembly:

    NOTE: If manifold does not fit flush against the burner, do not force the manifold on the burner assembly. The burners are not fully seated forward in the burner assembly. Remove the manifold and check burner positioning in the burner assembly assembly be

    NOTE: Use propane-resistant pipe dope to prevent leaks. Do not use Teflon tape.

    WARNING: FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available so

    Servicing Hot Surface Igniter

    The igniter does NOT require annual inspection. Check igniter resistance before removal. Refer to Fig. 62, 64 and 68.

    Remove igniter assembly

    Flushing Collector Box and Drainage System

    WARNING: ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or s

    NOTE: Ensure the pressure switch tube disconnected from the pressure switch is higher than the collector box opening or water will flow out of tube.

    NOTE: Do NOT blow into tube with tube connected to the pressure switch.

    Cleaning Condensate Drain and Trap

    NOTE: If the condensate trap is removed, a new gasket between the trap and collector box is required. Verify a condensate trap gasket is included in the service kit or obtain one from your local distributor.

    NOTE: If condensate has a heat pad attached to the trap, trace the wires for the pad back to the connection point and disconnect the wires for the heat pad.

    To re-install Condensate Drain and Trap:

    Checking Heat Pad Operation (If Applicable)

    In applications where the ambient temperature around the furnace is 32_F or lower, freeze protection measures are required. If this application is where heat tape has been applied, check to ensure it will operate when low temperatures are present.

    NOTE: The Heat Pad, when used, should be wrapped around the condensate drain trap. There is no need to use heat tape within the furnace casing. Most heat tapes are temperature activated, and it is not practical to verify the actual heating of the tape. Ch

    Cleaning Heat Exchangers

    The following items must be performed by a qualified service technician.

    Primary Heat Exchangers

    If the heat exchangers get an accumulation of light dirt or dust on the inside, they may be cleaned by the following procedure:

    NOTE: If the heat exchangers get a heavy accumulation of soot and carbon, both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design. A build--up of soot and carbon indicates

    WARNING: ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death, or property damage. Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF positi

    WARNING:ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Turn off the gas and electrical supplies to the furnace and install lockout tag before performing any maintenance or se

    NOTE: Burner cover, manifold, gas valve, and burner assembly should be removed as one assembly.

    NOTE: After cleaning, inspect the heat exchangers to ensure they are free of all foreign objects that may restrict flow of combustion products

    WARNING:FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage. Never purge a gas line into a combustion chamber. Never test for gas leaks with an open flame. Use a commercially available soa

Source: Carrier

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.