Medical Marijuana Facilities Checklist & Requirements

This inspection checklist is intended to assist the medical cannabidiol dispensary in becoming operational. . It also contains information that the Office of Medical Cannabidiol will monitor for regulatory compliance as the dispensary continues operations.
MaintainX
07/19/2022

Medical Marijuana Facilities Checklist & Requirements

This inspection checklist is intended to assist the medical cannabidiol dispensary in becoming operational. . It also contains information that the Office of Medical Cannabidiol will monitor for regulatory compliance as the dispensary continues operations.

    GENERAL REQUIREMENTS

    All Medical Marijuana (MMJ) facilities must be pre-approved for a Business License before applying for a construction or tenant improvement permit.

      In addition to this Checklist, a fully completed Development Services Permit Application and project plans shall be submitted to the Long Beach Development Permit Center. All sheet(s) of the plan(s) shall be stamped and signed by a professional engineer or architect before submittal.

        Did you include the type and quantity of MMJ products for dispensation, cultivation, manufacture, and testing in your Business License Application?

        • Yes
        • No
        • N / A

        Did you include the SDS sheets for the all chemicals/hazardous materials to exist at the facility?

        • Yes
        • No
        • N / A

        Is all proposed equipment listed and approved by a certified testing lab?

        • Yes
        • No
        • N / A

        Do the plans clearly show:

          The nature of occupancy, use, and construction type of the facility and adjacent spaces

          • Yes
          • No
          • N / A

          The business name

          • Yes
          • No
          • N / A

          The type of facility signage

          • Yes
          • No
          • N / A

          All the hardware on all the doors

          • Yes
          • No
          • N / A

          Access and egress from the facility and security features (i.e., locking devices, access control on entry doors & delayed access on exit door) * Location of Knox Box adjacent to the entry door

          • Yes
          • No
          • N / A

          Location & size of electrical service

          • Yes
          • No
          • N / A

          Consideration of plan layout (e.g., width of aisles proposed, unisex restroom if project is <1,500 ft2, etc.)

          • Yes
          • No
          • N / A

          Fire protection, fire sprinkler

          • Yes
          • No
          • N / A

          Fire alarm systems

          • Yes
          • No
          • N / A

          Location of fire extinguishers (2A10)

          • Yes
          • No
          • N / A

          Gas detection system

          • Yes
          • No
          • N / A

          If the selling of food, storage of edibles, and/or vape products is proposed

          • Yes
          • No
          • N / A

          Consideration of odor control and filtration

          • Yes
          • No
          • N / A

          Consideration of environmental issues

          • Yes
          • No
          • N / A

          Consideration of testing of MMJ products

          • Yes
          • No
          • N / A

          Propane use? (Indoor propane use is not allowed in Long Beach)

          • Yes
          • No
          • N / A

          If rack storage is proposed. High pile racks require a separate permit

          • Yes
          • No
          • N / A

          Finish schedule for floors, walls, & ceilings for all rooms provided

          • Yes
          • No
          • N / A

          Listing of all proposed plumbing fixtures provided (e.g., hand sinks, janitorial sinks, three compartment sinks, etc.)

          • Yes
          • No
          • N / A

          SPECIFIC REQUIREMENTS - DISPENSARY (ONLY)

          Do the plans clearly show:

            Consideration of natural and mechanical ventilation (10 persons/1000 ft.2 and 15 cfm per person)

            • Yes
            • No
            • N / A

            Fire separation? (Generally, no fire separation is required unless the storage area exceeds 10% of the occupancy.)

            • Yes
            • No
            • N / A

            Health Department approval if edibles are displayed or prepared

            • Yes
            • No
            • N / A

            SPECIFIC REQUIREMENTS – CULTIVATION FACILITY (ONLY)

            Do the plans clearly show:

              Consideration given to health and environmental issues

              • Yes
              • No
              • N / A

              Consideration of minimum and maximum areas * In new buildings or buildings where a change of occupancy occurred, fire sprinklers will be required where the area exceeds 12,000 ft.2

              • Yes
              • No
              • N / A

              The location of aisles and exit pathways inside the building * Hanging non-fire rated plastics are not allowed; Fire resistant vinyl shall be used only if such separation of spaces are proposed

              • Yes
              • No
              • N / A

              CO2 detection systems shall be connected to the buildings existing/new fire alarm or sprinkler monitoring system

              • Yes
              • No
              • N / A

              The location and process of drying the buds

              • Yes
              • No
              • N / A

              The fertilizers or chemicals being stored at the facility

              • Yes
              • No
              • N / A

              Electrical power needs and associated wiring diagram

              • Yes
              • No
              • N / A

              Electrical loads and wiring size for grow lighting, fans, etc.

              • Yes
              • No
              • N / A

              Natural and mechanical ventilation (10 persons/1000 ft.2 and 60 cfm per person)

              • Yes
              • No
              • N / A

              Consideration of odor and air filtration

              • Yes
              • No
              • N / A

              Consideration of water and sewer issues

              • Yes
              • No
              • N / A

              CO2 enrichment systems, if any. Anchorage for CO2 tanks and a listed CO2 detection system

              • Yes
              • No
              • N / A

              Cultivation waste management program in accordance with state & federal regulations

              • Yes
              • No
              • N / A

              Pesticide use at the facility in accordance with the product label

              • Yes
              • No
              • N / A

              SPECIFIC REQUIREMENTS – MANUFACTURING FACILITY (Only)

              Do the plans show:

                Consideration for natural and mechanical ventilation (10 persons/1000 ft.2 and 15 cfm per person)

                • Yes
                • No
                • N / A

                All fuel tanks (must be approved by Fire Department)

                • Yes
                • No
                • N / A

                All proposed equipment (must be listed by approved agencies)

                • Yes
                • No
                • N / A

                Health and environmental considerations

                • Yes
                • No
                • N / A

                Edible food items produced on the premises? Consider air supply and a Type I hood

                • Yes
                • No
                • N / A

                All waste product (must be stored, transported and disposed of in accordance with state and federal regulation)

                • Yes
                • No
                • N / A

                CO2 detection systems (must be connected to the buildings existing/new fire alarm or sprinkler monitoring system)

                • Yes
                • No
                • N / A

                Consideration of minimum and maximum areas * In new buildings or buildings where a change of occupancy occurred fire sprinklers will be required where the area exceeds 12,000 ft.2

                • Yes
                • No
                • N / A

                If plant oil extraction will be performed are the extraction processes, type of equipment, mechanical exhaust system, and room construction details documented

                • Yes
                • No
                • N / A

                SUMMARY

                Job Address

                Permit #

                Contractor/Installer

                License # & Class

                Signature

                Click here to sign

                Date

                Phone #

                Reference: https://www.longbeach.gov/globalassets/lbds/media-library/documents/building--safety/inspections/inspections/medical-marijuana-checklist

                Source: MaintainX (Community Member)

                Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.