    CAUTION: Prior to any of the following maintenance procedures, shut off all power to the unit. Failure to do so could cause personal injury.

    Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

    Periodic maintenance normally consists of changing or cleaning filters and (under some conditions) cleaning the main burners.

    FILTERS

    MOTORS

    Indoor Fan Motors

    CAUTION: Damage can occur if the bearings are over lubricated. Use grease sparingly.

    To go to bypass mode, the bypass VFD as installed in this unit must be switched by hand on the front of the bypass enclosure in the fan cabinet of the rooftop unit. It does not automatically go to bypass mode if the drive fails.

    The switches on the front of the bypass box control its run mode. For normal running:

    CAUTION: If the unit is operated with the manual bypass switch in the LINE (BYPASS) position and there are VAV boxes present, the boxes must be driven to the full-open position using a customer-supplied power source to prevent over-pressuring the ductwork

    WARNING! Perform all maintenance operations on the blower motor with power disconnected from the unit. Do not attempt to lubricate bearings with the unit in operation.

    TABLE 59: INDOOR BLOWER BEARING LUBRICATION SCHEDULE

    If desired, every three years remove both pipe plugs at each end shell and clean out any hardened grease or foreign matter

    FAN DRIVES

    OUTDOOR COIL

    NOTE: Exercise care when cleaning the coil so that the coil fins are not damaged.

    Do not permit the hot condenser air discharge to be obstructed by overhanging structures or shrubs.

    GAS BURNER

    TO CLEAN BURNERS

    COMBUSTION AIR DISCHARGE

    CLEANING FLUE PASSAGES AND HEATING ELEMENTS

    With proper combustion adjustment, the heating element of a gas fired furnace will seldom need cleaning. If the element should become sooted, it can be cleaned as follows:

    FIGURE 48 - TYPICAL FLUE BAFFLE

    The restrictor plate must also be sealed to furnace tube sheet.

    SECURE OWNERS APPROVAL

    When the system is functioning properly, secure the owner’s approval. Show him the location of all disconnect switches and the room temperature sensors. Teach him how to start and stop the unit and how to adjust the temperature settings within the limitat

Source: York

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.