Daikin Vision Semi-Custom Indoor Air Handler (Vision Extended Sizes CAC/CAH): Every 2000 Hours Maintenance

MaintainX
10/24/2021

Daikin Vision Semi-Custom Indoor Air Handler (Vision Extended Sizes CAC/CAH): Every 2000 Hours Maintenance

    Ball Bearing Lubrication

    CAUTION!

    Bearing overheating potential. Can damage the equipment. Do not over lubricate bearings. Use only a high grade mineral grease with a 200°F safe operating temperature. See below for specific recommended lubricants.

    Motor Bearings

    Supply and return fans—Supply and return fan motors should have grease added after every 2000 hours of operation. Using the following procedure, re-lubricate the bearings while the motor is warm, but not running.

    Use one of the greases shown in Table 35.

    Fan Shaft Bearings

    Any good quality lithium or lithium complex base grease, using mineral oil, conforming to NLGI grade 2 consistency, and an oil viscosity of 455-1135 SUS at 100°F (100-200 cSt at 40°C) may be used for re-lubrication.

    Compatibility of grease is critical. Lubricatable bearings are supplied with grease fittings or zerks for ease of lubrication with hand or automatic grease guns. Always wipe the fitting and grease nozzle clean.

Source: Daikin

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.