Ventilation Checklist
Use this ventilation checklist to control the build-up of airborne contaminants to reduce worker exposure and the potential for fire and accidents.
Ventilation Checklist
Use this ventilation checklist to control the build-up of airborne contaminants to reduce worker exposure and the potential for fire and accidents.
Name:
School:
Unit Ventilator/AHU No:
Room or Area:
Date Completed:
Signature:
Click here to sign
OUTDOOR AIR INTAKES
Marked locations of all outdoor air intakes on a small floor plan (for Yes No N/A example, a fire escape floor plan)
Ensured that the ventilation system was on and operating in “occupied” mode .
ACTIVITY 1: OBSTRUCTIONS
Ensured that outdoor air intakes are clear of obstructions, debris, clogs, or covers
Installed corrective devices as necessary (e.g., if snowdrifts or leaves frequently block an intake)
ACTIVITY 2: POLLUTANT SOURCES
Checked ground-level intakes for pollutant sources (dumpsters, loading docks, and bus-idling areas)
Checked rooftop intakes for pollutant sources (plumbing vents; kitchen, toilet, or laboratory exhaust fans; puddles; and mist from air-conditioning cooling towers)
Resolved any problems with pollutant sources located near outdoor air intakes (e.g., relocated dumpster or extended exhaust pipe)
ACTIVITY 3: AIRFLOW
Obtained chemical smoke (or a small piece of tissue paper or light plastic)
Confirmed that outdoor air is entering the intake appropriately
SYSTEM CLEANLINESS
ACTIVITY 4: AIR FILTERS
Replaced filters per maintenance schedule
Shut off ventilation system fans while replacing filters (prevents dirt from blowing downstream)
Vacuumed filter areas before installing new filters
Confirmed proper fit of filters to prevent air from bypassing (flowing around) the air filter
Confirmed proper installation of filters (correct direction for airflow)
ACTIVITY 5: DRAIN PANS
Ensured that drain pans slant toward the drain (to prevent water from accumulating)
Cleaned drain pans
Checked drain pans for mold and mildew
ACTIVITY 6: COILS
Ensured that heating and cooling coils are clean
ACTIVITY 7: AIR-HANDLING UNITS, UNIT VENTILATORS
Ensured that the interior of air-handling unit(s) or unit ventilator (air-mixing chamber and fan blades) is clean
Ensured that ducts are clean
ACTIVITY 8: MECHANICAL ROOMS
Checked mechanical room for unsanitary conditions, leaks, and spills
Ensured that mechanical rooms and air-mixing chambers are free of trash, chemical products, and supplies
CONTROLS FOR OUTDOOR AIR SUPPLY
Ensured that air dampers are at least partially open (minimum position)
Ensured that minimum position provides adequate outdoor air for occupants
ACTIVITY 9: CONTROLS INFORMATION
Obtained and reviewed all design inside/outside temperature and humidity requirements, controls specifications, as-built mechanical drawings, and controls operations manuals (often uniquely designed)
ACTIVITY 10: CLOCKS, TIMERS, SWITCHES
Turned summer-winter switches to the correct position
Set time clocks appropriately
Ensured that settings fit the actual schedule of building use (including night/weekend use)
ACTIVITY 11: CONTROL COMPONENTS
Ensured appropriate system pressure by testing line pressure at both the occupied (day) setting and the unoccupied (night) setting
Checked that the line dryer prevents moisture buildup
Replaced control system filters at the compressor inlet based on the compressor manufacturer’s recommendation (for example, when you blow down the tank)
Set the line pressure at each thermostat and damper actuator at the proper level (no leakage or obstructions)
ACTIVITY 12: OUTDOOR AIR DAMPERS
Ensured that the outdoor air damper is visible for inspection
Ensured that the recirculating relief and/or exhaust dampers are visible for inspection
Ensured that the recirculating relief and/or exhaust dampers are visible for inspection
CONTROLS FOR OUTDOOR AIR SUPPLY (continued)
Checked that the outdoor air damper fully closes within a few minutes of shutting off appropriate air handler
Checked that the outdoor air damper opens (at least partially with no delay) when the air handler is turned on
If in heating mode, checked that the outdoor air damper goes to its minimum position (without completely closing) when the room thermostat is set to 85°F
If in cooling mode, checked that the outdoor air damper goes to its minimum position (without completely closing) when the room thermostat is set to 60°F and mixed air thermostat is set to 45°F
If the outdoor air damper does not move, confirmed the following items:
ACTIVITY 13: FREEZE STATS
Disconnected power to controls (for automatic reset only) to test continuity across terminals
Confirmed (if applicable) that depressing the manual reset button (usually red) trips the freeze stat (clicking sound indicates freeze stat was tripped)
Assessed the feasibility of replacing all manual reset freeze-stats with automatic reset freeze-stats
ACTIVITY 14: MIXED AIR THERMOSTATS
Ensured that the mixed air stat for heating mode is set no higher than 65°F
Ensured that the mixed air stat for cooling mode is set no lower than the room thermostat setting
ACTIVITY 15: ECONOMIZERS
Confirmed proper economizer settings based on design specifications or local practices
Checked that sensor on the economizer is shielded from direct sunlight
Ensured that dampers operate properly (for outside air, return air, exhaust/relief air, and recirculated air), per the design specifications
CONTROLS FOR OUTDOOR AIR SUPPLY
ACTIVITY 16: FANS
Ensured that all fans (supply fans and associated return or relief fans) that move outside air indoors continuously operate during occupied hours (even when room thermostat is satisfied)
AIR DISTRIBUTION
ACTIVITY 17: AIR DISTRIBUTION
Ensured that supply and return air pathways in the existing ventilation system perform as required
Ensured that passive gravity relief ventilation systems and transfer grilles between rooms and corridors are functioning
Made sure every occupied space has supply of outdoor air (mechanical system or operable windows)
Ensured that supply and return vents are open and unblocked
Modified the HVAC system to supply outside air to areas without an outdoor air supply
Modified existing HVAC systems to incorporate any room or zone layout and population changes
Moved all barriers (for example, room dividers, large free-standing blackboards or displays, bookshelves) that could block movement of air in the room, especially those blocking air vents
Ensured that unit ventilators are quiet enough to accommodate classroom activities
Ensured that classrooms are free of uncomfortable drafts produced by air from supply terminals
ACTIVITY 18: PRESSURIZATION IN BUILDINGS
Ensured that air flows out of the building (using chemical smoke) through windows, doors, or other cracks and holes in exterior wall (for example, floor joints, pipe openings)
EXHAUST SYSTEMS
ACTIVITY 19: EXHAUST FAN OPERATION
Checked (using chemical smoke) that air flows into exhaust fan grille(s)
If fans are running but air is not flowing toward the exhaust intake, check for the following:
ACTIVITY 20: EXHAUST AIRFLOW
Checked (using chemical smoke) that air is drawn into the room from adjacent spaces
Ensured that air is flowing toward the exhaust intake
ACTIVITY 21: EXHAUST DUCTWORK
Checked that the exhaust ductwork downstream of the exhaust fan (which is under positive pressure) is sealed and in good condition .
QUANTITY OF OUTDOOR AIR
ACTIVITY 22: OUTDOOR AIR MEASUREMENTS AND CALCULATIONS
Measured the quantity of outdoor air supplied (22a) to each ventilation unit
Calculated the number of occupants served (22b) by the ventilation unit under consideration
Divided outdoor air supply (22a) by the number of occupants (22b) to determine the existing quantity of outdoor air supply per person (22c)
ACTIVITY 23: ACCEPTABLE LEVELS OF OUTDOOR AIR QUANTITIES
Compared the existing outdoor air per person (22c) to the recommended levels in Table 1
Corrected problems with ventilation units that supplied inadequate quantities of outdoor air to ensure that outdoor air quantities (22c) meet the recommended levels in Table 1
Source: MaintainX (Community Member)