Daikin Destiny Commercial Indoor Air Handler MD5 VFD: Every 6-12 Months Maintenance
This procedure maintenance is for checking and cleaning your equipment's heatsink. If installed in an appropriate environment, the drive requires very little maintenance. This procedure lists the routine maintenance intervals recommended by Daikin.
Daikin Destiny Commercial Indoor Air Handler MD5 VFD: Every 6-12 Months Maintenance
This procedure maintenance is for checking and cleaning your equipment's heatsink. If installed in an appropriate environment, the drive requires very little maintenance. This procedure lists the routine maintenance intervals recommended by Daikin.
Maintenance:
Application:
Interval:
Instruction:
Heatsink
The heatsink fins accumulate dust from the cooling air. Since a dusty heatsink is less efficient at cooling the drive, overtemperature faults become more likely. In a “normal” environment (not dusty, not clean) check the heatsink annually, in a dusty environment check more often.
Clean the heatsink as follows (when necessary):
NOTE: If there is a risk of the dust entering adjoining equipment, perform the cleaning in another room.
Source: MaintainX (Community Member)