79907 | TN1 MIXER TANK Fibercel Packing Motor Check P.M.

One of the biggest ways to prevent failures is to make sure your equipment is properly aligned and balanced.These programs are designed to keep your maintenance costs low by preventing costly failures before they happen.
MaintainX
05/15/2022

79907 | TN1 MIXER TANK Fibercel Packing Motor Check P.M.

One of the biggest ways to prevent failures is to make sure your equipment is properly aligned and balanced.These programs are designed to keep your maintenance costs low by preventing costly failures before they happen.

    Date

    Equipment #

    Location

    Crew Member

    Downtime/Runtime

    Motor physical inspection. (cleanliness, fan guard, frame, mounting bolt tightness, conduit condition).

    • Pass
    • Flag
    • Fail

    Pecker head and its internal components inspection (for corrosion, loose connections, fraying).

    • Pass
    • Flag
    • Fail

    Check motor fan cowl and cooling fans

    • Pass
    • Flag
    • Fail

    Runtime bearing test (vibration, temp check,)

    • Pass
    • Flag
    • Fail

    Lube (grease if it has the fittings for it. 1 to 2 shots for small motor.3 to 4 shots for larger motor).

    • Pass
    • Flag
    • Fail

    Shaft Inspection (check for wear, position, key stock)

    • Pass
    • Flag
    • Fail

    Shaft Inspection (check for wear, position, key stock)

    • Pass
    • Flag
    • Fail

    Surroundings check. (ensure equipment is clear free of obstructions and hazards).

    • Pass
    • Flag
    • Fail

    Complete standard short to ground check. check each wire, including T1, T2, T3 and the ground wire. If the reading is infinite, your motor should be fine.

    • Pass
    • Flag
    • Fail

    Conduct standard Ohm check. Test T1 to T2, T2 to T3, and T1 to T3.

    • Pass
    • Flag
    • Fail

    Complete standard leg Voltage test. Test the incoming voltage, place one of the multimeter's probes on L1 and the other on L2. Allow the multimeter to display the voltage and then repeat the tests while probing L1 and L3, then L2 and L3.

    • Pass
    • Flag
    • Fail

    Conduct standard continuity test. Earth continuity and resistance test: Using a multimeter, measure the resistance between the body of the motor and the ground. You are looking for a reading of 0.5 ohms or less. Some standards may specify 0.1 ohms.

    • Pass
    • Flag
    • Fail

    Complete Running Amps Test. With the motor running, check the full load amps (FLA) with a suitable meter or preferably a clamp on meter and compare with the name plate FLA. Deviations from rated FLA could signify problems with the motor under test.

    • Pass
    • Flag
    • Fail

    Inspect disconnect (for damage, corrosion inside, etc.)

    • Pass
    • Flag
    • Fail
Source: MaintainX (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.