Back

Allied K-Series (15-25 KCB): Annual Maintenance

The annual maintenance procedure focuses on B-lubrication, filters and condenser oil. The main purpose of regular maintenance is to ensure that all equipment required for production is operating at 100% efficiency at all times.
MaintainX
08/24/2022

Allied K-Series (15-25 KCB): Annual Maintenance

The annual maintenance procedure focuses on B-lubrication, filters and condenser oil. The main purpose of regular maintenance is to ensure that all equipment required for production is operating at 100% efficiency at all times.

    VI-MAINTENANCE

    The unit should be inspected once a year by a qualified service technician.

    A-Filters

    Units are equipped with six 24 X 24 X 2” filters. Filters should be checked and replaced when necessary with filters of like kind and size. Take note of air flow direction marking on filter frame when reinstalling filters. See figure 20.

    B-Lubrication

    All motors used in KGA units are factory lubricated, no further lubrication is required.

    Blower shaft bearings are prelubricated. For extended bearing life, relubricate at least once every two years with a lithium base grease such as Alvania 3 (Shell Oil), Chevron BRB2 (Standard OIl) or Regal AFB2 (Texas Oil). Use a hand grease gun for lubrication. Add only enough grease to purge through the bearings so that a bead of grease appears at the seal lip contacts.

    • Screenshot2021-02-16at11.41.31AM.png

    D-Condenser Coil

    Clean condenser coil annually with detergent or commercial coil cleaner and inspect monthly during the cooling season.

    Condenser coils are made of one, two and three formed slabs. Dirt and debris may become trapped between the slabs. To clean between slabs, carefully separate coil slabs and wash them thoroughly. See figure 21. Flush coils with water following cleaning. NOTE - Remove all screws and gaskets prior to cleaning procedure and replace upon completion.

    E-Supply Air Blower Wheel

    Annually inspect supply air blower wheel for accumulated dirt or dust. Turn off power before attempting to remove access panel or to clean blower wheel.

    F-Electrical

Source: MaintainX (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.