Daikin Destiny Commercial Indoor Air Handler MD5 VFD: Every 6 Years Maintenance
This procedure is for replacing your equipment's drive module fan. If installed in an appropriate environment, the drive requires very little maintenance. This procedure lists the routine maintenance intervals recommended by Daikin.
Daikin Destiny Commercial Indoor Air Handler MD5 VFD: Every 6 Years Maintenance
This procedure is for replacing your equipment's drive module fan. If installed in an appropriate environment, the drive requires very little maintenance. This procedure lists the routine maintenance intervals recommended by Daikin.
Maintenance:
Application:
Interval:
Instruction:
Drive Module Fan Replacement
The drive module fan cools the heatsink. Fan failure can be predicted by the increasing noise from fan bearings and the gradual rise in the heatsink temperature in spite of heatsink cleaning. If the drive is operated in a critical part of a process, fan replacement is recommended once these symptoms start appearing. Replacement fans are available from Daikin. Do not use other than Daikin specified spare parts.
Frame Sizes R1—R4
To replace the fan:
Frame Sizes R5 and R6
To replace the fan:
Source: MaintainX (Community Member)