    Check water level

    The need to periodically check water level controls and the waterside of the pressure vessel cannot be overemphasized. Most instances of major boiler damage are the result of operating with low water, or the use of untreated (or incorrectly) treated water

    FIGURE 8-3. Low Water Cutoff

    Blow down boiler

    Steam Boiler

    The instructions on the low water cutoff plate on a steam boiler should be followed in accordance with a definite schedule.The controls normally function for long periods of time, which may lead to laxity in testing on the assumption that normal operation

    Warning: Safe operation of your boiler demands periodic inspection and maintenance of all low water cut-off devices. Open and inspect them at least once a month. Check operation frequently by stopping water flow to the boiler, allowing water level to lowe

    FIGURE 8-4. Replica of Low Water Cutoff Plate

    FIGURE 8-5. Low Water Cutoff Piping

    Hot Water Boiler

Source: Cleaver Brooks

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.