WeatherMaster® Single-Packaged Rooftop Units 48P: Periodical Maintenance (bi-monthly)

This procedure if for the periodical (bi-monthly) cleaning of your equipment. Periodical cleaning assures proper airflow and heating efficiency.
MaintainX
09/13/2022

WeatherMaster® Single-Packaged Rooftop Units 48P: Periodical Maintenance (bi-monthly)

This procedure if for the periodical (bi-monthly) cleaning of your equipment. Periodical cleaning assures proper airflow and heating efficiency.

    COMBUSTION-AIR BLOWERS (48P ONLY)

    Clean periodically to assure proper airflow and heating efficiency. Inspect blower wheel every fall and periodically during heating season. For the first heating season, inspect blower wheel bi-monthly to determine proper cleaning frequency.

    To inspect blower wheel:

    • Screenshot2021-01-19at2.33.28PM.png

    SUPPLY FAN AND POWER EXHAUST MOTOR PLATE

    Adjust using a 15/16-in. wrench on the adjusting bolts:

    • Screenshot2021-01-19at2.38.25PM.png

    IMPORTANT: When installing or replacing belts, always use a complete set of new, matched belts to prevent potential vibration problems. Mixing belts often results in premature breakage of the new belts.

    BELT INSTALLATION AND TENSIONING:

    NOTE: Check the tension at least twice during the first day of operation, as there is normally a rapid decrease in tension until the belts have run in. Check tension periodically thereafter and keep it at the recommended tension.

    With the correct belt tension, belts may slip and squeal momentarily on start-up. This slippage is normal and disappears after wheel reaches operating speed. Excessive belt tension shortens belt life and may cause bearing and shaft damage.

    PULLEY ALIGNMENT

    For proper belt life, the motor and fan pulleys must be properly aligned. To check, first turn off unit power. Place a straightedge against the motor and fan pulleys. See Fig. 52. If the pulleys are properly aligned, the straightedge should be parallel to the belts.

    If they are not parallel, check that the motor shaft and fan shaft are parallel. If they are not, adjust the motor plate adjusting bolts until they are.

    After verifying that the shafts are parallel:

    INSTALLING REPLACEMENT MOTOR PULLEY (SUPPLY FAN ONLY)

    To install a field-supplied replacement pulley:

    CONDENSER FAN ADJUSTMENT (ALL UNITS EXCEPT SIZE 035)

    • Screenshot2021-01-19at2.53.33PM.png
Source: MaintainX (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.