Allied K-Series (13 - 25 KCA): Maintenance
This procedure focuses on Condenser oils, E-Supply Blower Wheels, and Lubrication. The main purpose of regular maintenance is to ensure that all equipment required for production is operating at 100% efficiency at all times.
Allied K-Series (13 - 25 KCA): Maintenance
This procedure focuses on Condenser oils, E-Supply Blower Wheels, and Lubrication. The main purpose of regular maintenance is to ensure that all equipment required for production is operating at 100% efficiency at all times.
VI-MAINTENANCE
The unit should be inspected once a year by a qualified service technician.
A-Filters
Units are equipped with six 24 X 24 X 2” filters. Filters should be checked and replaced when necessary with filters of like kind and size. Take note of air flow direction marking on filter frame when reinstalling filters. See figure 20.
NOTE - Filters must be U.L.C. certified or equivalent for use in Canada.
B-Lubrication
D-Condenser Coil
Clean condenser coil annually with detergent or commercial coil cleaner and inspect monthly during the cooling season.
Condenser coils are made of one, two and three formed slabs. Dirt and debris may become trapped between the slabs. To clean between slabs, carefully separate coil slabs and wash them thoroughly. See figure 21. Flush coils with water following cleaning. NOTE - Remove all screws and gaskets prior to cleaning procedure and replace upon completion.
E-Supply Blower Wheel
Annually inspect supply air blower wheel for accumulated dirt or dust. Turn off power before attempting to remove access panel or to clean blower wheel.
F-Electrical
Source: MaintainX (Community Member)