Series R® Helical Rotary Chiller: Annual Maintenance

Annual maintenance is a simple and cost-effective way to ensure your HVAC system is running at peak efficiency and to catch problems before they get serious.
MaintainX
08/10/2022

Series R® Helical Rotary Chiller: Annual Maintenance

Annual maintenance is a simple and cost-effective way to ensure your HVAC system is running at peak efficiency and to catch problems before they get serious.

    Maintenance

    Perform all maintenance procedures and inspections at the recommended intervals. This will prolong the life of the chiller and minimize the possibility of costly failures.

    Use the “Operator’s Log”, such as that show in chapter “Log and Check Sheet,” p. 124 to record an operating history for unit. The log serves as a valuable diagnostic tool for service personnel. By observing trends in operating conditions, an operator can anticipate and prevent problem situations before they occur. If unit does not operate properly during maintenance inspections, see “Diagnostics,” p. 103.

    After unit has been operating for approximately 30 minutes and system has stabilized, check the operating conditions and complete procedures below:

    Annual

    Annual Procedures:

    ! WARNING

    Hazardous Voltage w/Capacitors!

    Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for dis

    Refrigerant and Oil Charge Management

    Proper oil and refrigerant charge is essential for proper unit operation, unit performance, and environmental protection. Only trained and licensed service personnel should service the chiller.

    Note: Low temperature applications units will have values that vary from Table 60. Contact your local Trane office for more information.

    Table 60

    • Screenshot2021-01-22at6.29.41AM.png

      Note: Low temperature applications units will have values that vary from Table 60. Contact your local Trane office for more information.

      Lubrication System

      The lubrication system has been designed to keep most of the oil lines filled with oil as long as there is a proper oil level in the oil sump.

      Oil Sump Level Check

      Oil system consists of the following components:

      Note: It is recommended to check the oil level in the sump using a sight glass or a manometer, attached to charging hoses.

      • Screenshot2021-01-22at6.33.35AM.png

      Important: If levels are outside these ranges, contact your local Trane office.

      Condenser Maintenance

      Condenser Coil Cleaning

      ! WARNING

      Hazardous Chemicals!

      Failure to follow all safety instructions below could result in death or serious injury. Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with skin occurs. Handle chemical carefully and avoid contact with skin. ALWAYS wear Personal Protective Equipment (PPE) including goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recomme

      Clean the condenser coils at least once a year or more frequently if the unit is in a “dirty” environment. A clean condenser coil will help to maintain chiller operating efficiency. Follow the detergent manufacturer's instructions to avoid damaging the condenser coils.

      To clean the condenser coils use a soft brush and a sprayer such as a garden pump type or a high-pressure type. A high quality detergent such as Trane Coil Cleaner (Part No. CHM-00255) is recommended.

      Note: If detergent mixture is strongly alkaline (pH value greater than 8.5, an inhibitor must be added).

    Source: MaintainX (Community Member)

    Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.