Annual AHU Cooling Preventative Maintenance Inspection

This procedure is used to maintain AHU, this helps improve energy efficiency, air quality, lifespan and reduce risk of breakdowns and costly repairs.
Quest Diagnostics Atlanta
01/22/2025

Annual AHU Cooling Preventative Maintenance Inspection

This procedure is used to maintain AHU, this helps improve energy efficiency, air quality, lifespan and reduce risk of breakdowns and costly repairs.

    Quarterly Air Handler Maintenance for AHU-01

    Enter the date and time of the maintenance

    Shut unit down and perform safe LOTO

    • Pass
    • Flag
    • Fail

    Check and tighten all electrical connections

    • Pass
    • Flag
    • Fail

    Check condition of control contacts for wear, pitting, and erosion

    • Pass
    • Flag
    • Fail

    Check all operating/safety controls

    • Pass
    • Flag
    • Fail

    Check and clean condensate drain pan and lines

    • Pass
    • Flag
    • Fail

    Check condensate pump if applicable

    • Pass
    • Flag
    • Fail

    Check chilled water coil/ clean surface per contract where applicable

    • Pass
    • Flag
    • Fail

    Check valves/ actuators where applicable

    • Pass
    • Flag
    • Fail

    Check dampers/ linkages

    • Pass
    • Flag
    • Fail

    Check damper actuators

    • Pass
    • Flag
    • Fail

    Check economizer operation

    • Pass
    • Flag
    • Fail

    Check filters and replace per contract

    • Pass
    • Flag
    • Fail

    Check belts and replace per contract

    • Pass
    • Flag
    • Fail

    Check blower wheels/ clean surface

    • Pass
    • Flag
    • Fail

    Check sheaves wear/ alignment

    • Pass
    • Flag
    • Fail

    Check and lubricate vanes, linkages, bearings, etc.

    • Pass
    • Flag
    • Fail

    Check and verify volts/ amps of blower motor

    • Pass
    • Flag
    • Fail

    Check for any unusual noises/ vibrations

    • Pass
    • Flag
    • Fail

    Check and verify cabinetry hardware conditions

    • Pass
    • Flag
    • Fail

    Check overall condition of unit

    • Pass
    • Flag
    • Fail

    Record the volts/ amps of supply blower motor

    Record the volts/ amps of return blower motor

    Record the supply and return air temperatures

    Record the static pressure across filters and coils

    Technician's signature upon completion

    Click here to sign
Source: Quest Diagnostics Atlanta (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.