MONTHLY FIRE PUMP CHURN

The weekly or monthly no-flow (churn) test is an important part of ensuring that a fire pump can be continually relied upon in the event of a fire. These tests will help to ensure that the pump will start and will not overheat in the event of a fire.
DC09-New Lenox IL - Michaels
06/25/2024

MONTHLY FIRE PUMP CHURN

The weekly or monthly no-flow (churn) test is an important part of ensuring that a fire pump can be continually relied upon in the event of a fire. These tests will help to ensure that the pump will start and will not overheat in the event of a fire.

    Notify your local alarm company of a pending churn test.

    • Pass
    • Flag
    • Fail

    Verify the fire pump churn test by checking the test log.

    • Pass
    • Flag
    • Fail

    Make sure the jockey pump is shut off. This is the small pump in the system that keeps pressure in the system's piping.

    • Pass
    • Flag
    • Fail

    Check drainage of the drip pockets under the packing gland. Check the packing adjustment drip so that lubrication is maintained. It should be about one drop per second.

    • Pass
    • Flag
    • Fail

    Place a five-gallon bucket to catch water under the small pet valve that controls pressure. This valve is on the side or under the pump controller.

    • Pass
    • Flag
    • Fail

    Begin to allow pressure to drop by opening the small pet cock valve. Note the pressure beginning to drop in response to the opening of the valve in the log. The pump will start to work automatically. Close the small pet cock valve once the pump starts.

    • Pass
    • Flag
    • Fail

    Find the ideal churn pressure on the nameplate of the pump. Note this ideal pressure in the log. Take the difference between the suction gauge reading and the discharge gauge reading to find the churn pressure. Note the suction gauge pressure, discharge pressure and the actual or found churn pressure in the log. The found churn pressure should match the ideal pressure noted in the log.

    • Pass
    • Flag
    • Fail

    Observe the packing glands to make sure they are still leaking freely to cool the packing off. Note this on the log. Note in the log that the casing relief valve begins to drain while the pump is running to keep pump case from overheating.

    • Pass
    • Flag
    • Fail

    Let the pump run for seven minutes, then shut it off for seven minutes. Make a note in the log if no adverse conditions were found during the test.

    • Pass
    • Flag
    • Fail

    After Finishing<br />Reset the fire pump to automatic.<br />Reset the jockey pump to automatic.

    • Pass
    • Flag
    • Fail

    Bring any adverse conditions to the attention of the facility manager.<br />Sign and date the test log

    • Pass
    • Flag
    • Fail

    Signature

    Click here to sign

    Take Photo of Asset Prior to Closing

    Add or drag pictures
Source: DC09-New Lenox IL - Michaels (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.