Back

Axiom™ Vertical Stack Water Source Heat Pump: Preventive Maintenance

This procedure is for the preventive maintenance of your unit. It has been simplified and has a list of preventive suggestions that focuses on your equipment's filter.
MaintainX
08/06/2022

Axiom™ Vertical Stack Water Source Heat Pump: Preventive Maintenance

This procedure is for the preventive maintenance of your unit. It has been simplified and has a list of preventive suggestions that focuses on your equipment's filter.

    Preventive Maintenance

    Maintenance on the unit is simplified with the following preventive suggestions:

    • Screenshot2021-01-26at12.40.26PM.png

    ! WARNING

    Hazardous Voltage!

    Failure to disconnect power before servicing could result in death or serious injury.

    Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.

    Check the contactors and relays within the control panel at least once a year. It is good practice to check the tightness of the various wiring connections within the control panel.

    A strainer (60 mesh or greater) must be used on an open loop system to keep debris from entering the unit heat exchanger and to ensure a clean system.

    For units on well water, it is important to check the cleanliness of the water-to-refrigerant heat exchanger. Should it become contaminated with dirt and scaling as a result of bad water, the heat exchanger will have to be back flushed and cleaned with a chemical that will remove the scale. This service should be performed by an experienced service person.

    ! WARNING

    Hazardous Chemicals!

    Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with skin or eyes occurs.

    Handle chemical carefully and avoid contact with skin. ALWAYS wear Personal Protective Equipment (PPE) including goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices.

    It should be noted that the water quality should be checked periodically.

    • Screenshot2021-01-26at12.42.40PM.png
Source: MaintainX (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.