HomeIndustries Use Cases PricingResources Book a TourLog In to MaintainXIndustries Use Cases PricingResources Book a TourLog In to MaintainX Back Manufacturing / Industrial • MaintenanceQSK60G with AGC-4 Cummins Application - Maintenance - DailyMaintainX10/24/2021QSK60G with AGC-4 Cummins Application - Maintenance - DailyAIR INTAKE MAINTENANCECheck air cleaner restriction indicator (where fitted)If the service indicator shows red, replace air cleaner elements and reset the air cleaner service indicator.Check air intake system for leaksVisually inspect the air intake system for signs of wear or damage.Check audibly when the generator set is running. To replace, contact your authorized distributorCOOLING MAINTENANCECheck coolant level of radiatorIf low, top up to coolant system specifications level, with Cummins recommended coolant mix.Check cooling fan blades and motorsVisually inspect the fan blades through the guarding for signs of wear or damage. To replace, contact your authorized distributor.Check coolant lines and radiator hoses for leaks, wear, and cracksVisually check for leaks, worn or damages hoses. To replace, contact your authorized distributor.Check radiator air flowVisually inspect the radiator through the guarding for blockage, build up of debris, signs of wear or damage. To clean or replace, contact your authorized distributor.CONTROL MAINTENANCECheck operation of Control PanelCheck display (the system will perform a control panel test on initial activation). To replace, contact your authorized distributor.TYPICAL ENGINE MAINTENANCE - C1400 N5C STANDARD PIPELINE GASAir Cleaner Restriction Indicator - CheckControl Panel Assembly - CheckCoolant Level - CheckFan, Cooling - Inspect for ReuseLubricating Oil Level - Check.EXHAUST MAINTENANCECheck all exhaust components, and hardware (fittings, clamps, fasteners, etc.)Visually inspect the exhaust system for signs of wear or damage. Check audibly when the generator set is running. To replace, contact your authorized distributor.Check exhaust condensation trapDrain condensation into a suitable container. Dispose of fluids in accordance with local legislation.GENERATOR SET MAINTENANCECheck fuel level in tank: If low, add fuel (A full tank reduces condensation.)Check bedframe/enclosure fluid containment (where fitted)Drain as necessary. Clean all contaminated areas. Dispose of fluids in accordance with local legislation.Check generator set enclosureVisually check enclosure, walk around inspection of generator set.Make sure no inlets/outlets are covered/restricted, service access doors are operational and safety systems are in place and operational.To replace damaged parts, contact your authorized distributor.Source: Cummins (quickserve.cummins.com)
Back Manufacturing / Industrial • MaintenanceQSK60G with AGC-4 Cummins Application - Maintenance - DailyMaintainX10/24/2021QSK60G with AGC-4 Cummins Application - Maintenance - DailyAIR INTAKE MAINTENANCECheck air cleaner restriction indicator (where fitted)If the service indicator shows red, replace air cleaner elements and reset the air cleaner service indicator.Check air intake system for leaksVisually inspect the air intake system for signs of wear or damage.Check audibly when the generator set is running. To replace, contact your authorized distributorCOOLING MAINTENANCECheck coolant level of radiatorIf low, top up to coolant system specifications level, with Cummins recommended coolant mix.Check cooling fan blades and motorsVisually inspect the fan blades through the guarding for signs of wear or damage. To replace, contact your authorized distributor.Check coolant lines and radiator hoses for leaks, wear, and cracksVisually check for leaks, worn or damages hoses. To replace, contact your authorized distributor.Check radiator air flowVisually inspect the radiator through the guarding for blockage, build up of debris, signs of wear or damage. To clean or replace, contact your authorized distributor.CONTROL MAINTENANCECheck operation of Control PanelCheck display (the system will perform a control panel test on initial activation). To replace, contact your authorized distributor.TYPICAL ENGINE MAINTENANCE - C1400 N5C STANDARD PIPELINE GASAir Cleaner Restriction Indicator - CheckControl Panel Assembly - CheckCoolant Level - CheckFan, Cooling - Inspect for ReuseLubricating Oil Level - Check.EXHAUST MAINTENANCECheck all exhaust components, and hardware (fittings, clamps, fasteners, etc.)Visually inspect the exhaust system for signs of wear or damage. Check audibly when the generator set is running. To replace, contact your authorized distributor.Check exhaust condensation trapDrain condensation into a suitable container. Dispose of fluids in accordance with local legislation.GENERATOR SET MAINTENANCECheck fuel level in tank: If low, add fuel (A full tank reduces condensation.)Check bedframe/enclosure fluid containment (where fitted)Drain as necessary. Clean all contaminated areas. Dispose of fluids in accordance with local legislation.Check generator set enclosureVisually check enclosure, walk around inspection of generator set.Make sure no inlets/outlets are covered/restricted, service access doors are operational and safety systems are in place and operational.To replace damaged parts, contact your authorized distributor.Source: Cummins (quickserve.cummins.com)