AERO® Semi-Custom Central Station Air Handler 39M: Filter Maintenance

This annual procedure focuses on different kinds of your equipment's filters and in-track baffles. This will help ensure that your unit performs at it's peak for a long period of time.
MaintainX
09/09/2022

AERO® Semi-Custom Central Station Air Handler 39M: Filter Maintenance

This annual procedure focuses on different kinds of your equipment's filters and in-track baffles. This will help ensure that your unit performs at it's peak for a long period of time.

    Filters

    Air filters should be inspected regularly and changed when dirty. Filter life can vary greatly from one unit to another, depending upon the application and the amount of contaminants in the return and ventilation air entering the air handler. Each job should be evaluated and maintenance schedules established accordingly. At a minimum, the filters should be changed at the beginning of the cooling and heating seasons.

    Although not a direct part of the air handler, outdoor air inlet screens and/or grilles that may be present should also be checked regularly and cleaned as necessary. They can easily become plugged with debris, grease, or other contaminants, depending

    upon their location. This reduces the availability of ventilation air, which can contribute to indoor air quality problems.

    All filter sections use adjustable blank-off plates to close off any airway area not filled with filter media. Check blank-off plates to prevent unfiltered air from bypassing the filters. Blank-off plates must be on door side of unit.

    BAG-CARTRIDGE FILTERS

    • Screenshot2021-01-13at3.20.43PM.png
    • Screenshot2021-01-13at3.23.25PM.png
    • Screenshot2021-01-13at3.20.43PM.png

    IN-TRACK BAFFLES

    Filter sections are shipped with adjustable in-track baffles. When installed properly as shown in Fig. 201 and 202, the baffles close off empty space in the track preventing air from bypassing the fil- ters.

    • Screenshot2021-01-13at3.25.26PM.png
    • Screenshot2021-01-13at3.25.58PM.png

    FLAT FILTERS

    ANGLE FILTERS

    • Screenshot2021-01-13at3.30.00PM.png

    HEPA FILTERS

    • Screenshot2021-01-13at3.32.12PM.png

    Filter arrangements are shown in Fig. 206-210.

Source: MaintainX (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.