Steam Trap Quarterly

Verify proper operation of all steam traps by audible check or temperature differential between trap inlet and outlet.
47 Minneapolis MN
02/25/2025

Steam Trap Quarterly

Verify proper operation of all steam traps by audible check or temperature differential between trap inlet and outlet.

    Inspection

    Steam Tunnel Supply Line

    Record Temperature Differential. (Subtract Outlet Temperature from Inlet Temperature. Minimum Δ: 80°)

    if the answer is "> 79 "
    if the answer is "< 80 "

    Steam Tunnel Drip Leg

    Record Temperature Differential. (Subtract Outlet Temperature from Inlet Temperature. Minimum Δ: 80°)

    if the answer is "> 79 "
    if the answer is "< 80 "

    Steam Header Above Unload Conveyor

    Record Temperature Differential. (Subtract Outlet Temperature from Inlet Temperature. Minimum Δ: 80°)

    if the answer is "> 79 "
    if the answer is "< 80 "

    Steam Header Above Pony Washers

    Record Temperature Differential. (Subtract Outlet Temperature from Inlet Temperature. Minimum Δ: 80°)

    if the answer is "> 79 "
    if the answer is "< 80 "

    Steam Header Above Washer 8

    Record Temperature Differential. (Subtract Outlet Temperature from Inlet Temperature. Minimum Δ: 80°)

    if the answer is "> 79 "
    if the answer is "< 80 "

    Feed Water Tank Steam Heater

    Record Temperature Differential. (Subtract Outlet Temperature from Inlet Temperature. Minimum Δ: 80°)

    if the answer is "> 79 "
    if the answer is "< 80 "

    Steam Heater Supply Line

    Record Temperature Differential. (Subtract Outlet Temperature from Inlet Temperature. Minimum Δ: 80°)

    if the answer is "> 79 "
    if the answer is "< 80 "

    Steam Heater

    Verify proper operation by performing audible check with mechanic stethoscope. Steam trap should be heard intermittently discharging or a steady "bubbling" through the bucket vent if under low load. (Expect this steam trap to be under low load due to it's location downstream of Steam Heater Spence Valve.)

    if the answer is "oneOf [Quarterly Inspection Failed.]"

    Steam Trap Quarterly Inspection

    • Pass
    • Flag
    • Fail
Source: 47 Minneapolis MN (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.