Daily Critical Reliability Checklist
Critical items are meticulously recorded daily for safety and operational assurance.
Daily Critical Reliability Checklist
Critical items are meticulously recorded daily for safety and operational assurance.
*** LOTO Confirmation Statement - DO NOT EDIT/REMOVE ***
All hazardous energy has been isolated using LOTO procedures?
All potential stored or residual energy has been relieved, disconnected, restrained, lowered, and/or otherwise rendered safe?
Record Boiler Pressure (75 - 100 PSI)
Record Tempered Water Temperature (70 - 100 F)
Record Hot Water Temperature (140 - 160 F)
Record Boiler Stack Temperature Maximum 475 F
Check Boiler Chemical Levels
Record Feed Water Tank Temperature (180 - 200 F)
Test Low Water Cut Off Alarm. Document on FM Global Red Tag
Record Polishing Softener Water Hardness (0 PPM)
Record Main Water Softeners Hardness Levels ( <3 Grains)
Record Temperature Of City Water In
Record Temperature Of City Water Out
Record Temperature Of WW In
Record Temperature Of WW Out
Calculate & Record Approach Reading (WW In - City Water Out)
Record Compressor 1 Pressure (100 - 125 PSI)
Record Compressor 1 Air End Temperature
Record Compressor 2 Pressure (100 - 125 PSI)
Record Compressor 2 Air End Temperature
Check Compressor Cooling Air Filter Present/Clean
Check Oil Level Normal (OEM Specified)
Record City Electric Meter Reading
Record City Gas Meter Reading
Record City Water Meter Reading
Record Sewer Meter Reading (If Applicable)
Source: 087 San Antonio TX - Cintas (Community Member)