Omnizone™ Constant Volume Water-Cooled Cooling Unit 50BVZ: 6 Months Maintenance
This procedure has the recommended guidelines for the bi-monthly maintenance of your unit. The given instruction is only a recommended guideline.
Omnizone™ Constant Volume Water-Cooled Cooling Unit 50BVZ: 6 Months Maintenance
This procedure has the recommended guidelines for the bi-monthly maintenance of your unit. The given instruction is only a recommended guideline.
Fan Motor Lubrication
The fan motor was properly lubricated at the time of manufacture.
IMPORTANT: PILLOW BLOCK STYLE FAN BEARINGS: Bearings have been prelubricated with high quality grease. Bearings must be relubricated once every 6 months or every 2500 hours of operation, whichever comes first.
Fan Bearing Lubrication
Inspect the fan bearings for proper lubrication every 6 month or 2500 hours of operation, whichever comes first. Standard units have grease fittings on the fan shaft bearings, located on each side of the blower wheel.
Source: MaintainX (Community Member)