Gas train safety checks, Monthly
Periodically check that the HIGH and LOW gas pressure safety switches on the gas train are functioning properly
Gas train safety checks, Monthly
Periodically check that the HIGH and LOW gas pressure safety switches on the gas train are functioning properly
Gas train assembly LOW gas pressure safety switch test
Section #1
To check the LOW pressure switch operation, slowly increase the LOW pressure switch setting from its standard setting of 3 inches water column with the burner operating. At some point the burner should shut down and a LOW gas pressure fault should be indicated on the CRT screen. Position the LOW pressure switch back to 3 inches water column. Proper operation of the LOW pressure safety switch has now been verified
To check the HIGH pressure switch operation, slowly decrease the HIGH pressure switch setting from its standard setting of 15 inches water column with the burner operating. At some point the burner should shut down and a HIGH gas pressure fault should be indicated on the CRT screen. Position the HIGH pressure switch back to 15 inches water column. Proper operation of the HIGH pressure safety switch has now been verified.
Sign when completed
Click here to sign
Source: Quality Holdings LLC (Community Member)