Gas train safety checks, Monthly

Periodically check that the HIGH and LOW gas pressure safety switches on the gas train are functioning properly
Quality Holdings LLC
11/28/2022

Gas train safety checks, Monthly

Periodically check that the HIGH and LOW gas pressure safety switches on the gas train are functioning properly

    Gas train assembly LOW gas pressure safety switch test

    Section #1

    To check the LOW pressure switch operation, slowly increase the LOW pressure switch setting from its standard setting of 3 inches water column with the burner operating. At some point the burner should shut down and a LOW gas pressure fault should be indicated on the CRT screen. Position the LOW pressure switch back to 3 inches water column. Proper operation of the LOW pressure safety switch has now been verified

    To check the HIGH pressure switch operation, slowly decrease the HIGH pressure switch setting from its standard setting of 15 inches water column with the burner operating. At some point the burner should shut down and a HIGH gas pressure fault should be indicated on the CRT screen. Position the HIGH pressure switch back to 15 inches water column. Proper operation of the HIGH pressure safety switch has now been verified.

    Sign when completed

    Click here to sign
Source: Quality Holdings LLC (Community Member)

Please note that any procedure, checklist, or other document available in the MaintainX Procedure Hub is provided for general education and information only and does not constitute legal, medical, or financial advice. MaintainX makes the materials available AS IS and AS PROVIDED, without warranties of any kind. By downloading or using any such materials, you assume the risk that they may not be appropriate for your specific situation and agree that you are solely responsible for any such use, including compliance with applicable law and with meeting any conditions of product warranties.